Tap Off Unit
SRS TOU is designed for safe and efficient power tapping from main distribution cable systems. It offers both busbar and line tap solutions to suit various application needs.
< LV Switchgear
Tap Off Unit

Product Description
SRS TOU is designed for safe and efficient power tapping from main distribution cable systems. It offers both busbar and line tap solutions to suit various application needs.
General Specification
- Standard: IEC 60439-1 & -2, IEC 60529
- Rated Voltage: 415V/ 240V
- Rated Current: Up to 630A
- Rated Frequency: 50Hz
- Fault Level: Up to 25kA
- Rated Impulse Voltage Withstand: 8kV
- Form of Segregation: Up to Form 2B
- Degree of Protection (Indoor): Up to IP43
- Cable Entry: Top and Bottom
- Enclosure Type: Wall Mounted
- Accessibility: Front
General Specification
- Standard: IEC 60439-1 & -2, IEC 60529
- Rated Voltage: 415V/ 240V
- Rated Current: Up to 630A
- Rated Frequency: 50Hz
- Fault Level: Up to 25kA
- Rated Impulse Voltage Withstand: 8kV
- Form of Segregation: Up to Form 2B
- Degree of Protection (Indoor): Up to IP 43
- Cable Entry: Top and Bottom
- Enclosure Type: Wall Mounted
- Accessibility: Front